12 AWG aluminum voltage drop chart

55 ft at 20 ALongest 240 V single-phase run under 3% drop

V
A
ftDistance from the panel to the load, not round trip.

ResultsVoltage Drop

The short answer

12 AWG aluminum (6,530 circular mils) carrying 20 A on a 240 V single-phase circuit reaches 3% voltage drop at about 55 feet. At lighter loads it can go farther, as the tables below show.

Percent voltage drop at 240 V single-phase

Values over 3% are marked.

Load25 ft50 ft75 ft100 ft150 ft200 ft250 ft300 ft
5 A0.3%0.7%1%1.4%2%2.7%3.4%4.1%
10 A0.7%1.4%2%2.7%4.1%5.4%6.8%8.1%
15 A1%2%3%4.1%6.1%8.1%10.1%12.2%
20 A1.4%2.7%4.1%5.4%8.1%10.8%13.5%16.2%

Longest run that stays under 3%

Load120 V 1φ240 V 1φ208 V 3φ480 V 3φ
5 A111 ft222 ft222 ft512 ft
10 A55 ft111 ft111 ft256 ft
15 A37 ft74 ft74 ft171 ft
20 A28 ft55 ft55 ft128 ft

How it's calculated

Single-phase: VD = 2 × K × I × L ÷ CM Three-phase: VD = 1.732 × K × I × L ÷ CM K = 21.2 (aluminum), CM = 6,530 for 12 AWG

Table 310.16 lists 12 AWG aluminum at 15 A (60 °C) and 20 A (75 °C), before any 240.4(D) limit on the breaker size. Voltage drop is a separate check. On long runs it usually decides the wire size.