12 AWG copper voltage drop chart

73 ft at 25 ALongest 240 V single-phase run under 3% drop

V
A
ftDistance from the panel to the load, not round trip.

ResultsVoltage Drop

The short answer

12 AWG copper (6,530 circular mils) carrying 25 A on a 240 V single-phase circuit reaches 3% voltage drop at about 73 feet. At lighter loads it can go farther, as the tables below show.

Percent voltage drop at 240 V single-phase

Values over 3% are marked.

Load25 ft50 ft75 ft100 ft150 ft200 ft250 ft300 ft
5 A0.2%0.4%0.6%0.8%1.2%1.6%2.1%2.5%
10 A0.4%0.8%1.2%1.6%2.5%3.3%4.1%4.9%
15 A0.6%1.2%1.9%2.5%3.7%4.9%6.2%7.4%
20 A0.8%1.6%2.5%3.3%4.9%6.6%8.2%9.9%
25 A1%2.1%3.1%4.1%6.2%8.2%10.3%12.3%

Longest run that stays under 3%

Load120 V 1φ240 V 1φ208 V 3φ480 V 3φ
5 A182 ft364 ft365 ft842 ft
10 A91 ft182 ft182 ft421 ft
15 A61 ft121 ft122 ft281 ft
20 A46 ft91 ft91 ft210 ft
25 A36 ft73 ft73 ft168 ft

How it's calculated

Single-phase: VD = 2 × K × I × L ÷ CM Three-phase: VD = 1.732 × K × I × L ÷ CM K = 12.9 (copper), CM = 6,530 for 12 AWG

Table 310.16 lists 12 AWG copper at 20 A (60 °C) and 25 A (75 °C), before any 240.4(D) limit on the breaker size. Voltage drop is a separate check. On long runs it usually decides the wire size.

Other copper sizes

10 AWG · 14 AWG · 8 AWG · 6 AWG · 4 AWG · 2 AWG · 3 AWG · 1 AWG · 1/0 AWG · 2/0 AWG · 3/0 AWG · 4/0 AWG

Open the full voltage drop calculator with these numbers

Results are estimates for planning and education. Verify against the current code edition your jurisdiction has adopted, manufacturer data and a licensed professional before you build or install.