8 AWG copper voltage drop chart

92 ft at 50 ALongest 240 V single-phase run under 3% drop

V
A
ftDistance from the panel to the load, not round trip.

ResultsVoltage Drop

The short answer

8 AWG copper (16,510 circular mils) carrying 50 A on a 240 V single-phase circuit reaches 3% voltage drop at about 92 feet. At lighter loads it can go farther, as the tables below show.

Percent voltage drop at 240 V single-phase

Values over 3% are marked.

Load25 ft50 ft75 ft100 ft150 ft200 ft250 ft300 ft
15 A0.2%0.5%0.7%1%1.5%2%2.4%2.9%
20 A0.3%0.7%1%1.3%2%2.6%3.3%3.9%
25 A0.4%0.8%1.2%1.6%2.4%3.3%4.1%4.9%
30 A0.5%1%1.5%2%2.9%3.9%4.9%5.9%
40 A0.7%1.3%2%2.6%3.9%5.2%6.5%7.8%
50 A0.8%1.6%2.4%3.3%4.9%6.5%8.1%9.8%

Longest run that stays under 3%

Load120 V 1φ240 V 1φ208 V 3φ480 V 3φ
15 A154 ft307 ft307 ft709 ft
20 A115 ft230 ft231 ft532 ft
25 A92 ft184 ft184 ft426 ft
30 A77 ft154 ft154 ft355 ft
40 A58 ft115 ft115 ft266 ft
50 A46 ft92 ft92 ft213 ft

How it's calculated

Single-phase: VD = 2 × K × I × L ÷ CM Three-phase: VD = 1.732 × K × I × L ÷ CM K = 12.9 (copper), CM = 16,510 for 8 AWG

Table 310.16 lists 8 AWG copper at 40 A (60 °C) and 50 A (75 °C), before any 240.4(D) limit on the breaker size. Voltage drop is a separate check. On long runs it usually decides the wire size.

Other copper sizes

12 AWG · 10 AWG · 14 AWG · 6 AWG · 4 AWG · 2 AWG · 3 AWG · 1 AWG · 1/0 AWG · 2/0 AWG · 3/0 AWG · 4/0 AWG

Open the full voltage drop calculator with these numbers

Results are estimates for planning and education. Verify against the current code edition your jurisdiction has adopted, manufacturer data and a licensed professional before you build or install.